Scott T connection of Transformer

The Scott T connection of transformer is a method of converting three-phase electrical power into two-phase power and vice versa using two single-phase transformers.
It was first introduced by C. F. Scott and is therefore known as the Scott connection or T-T connection. It is commonly used in applications where three-phase and two-phase power systems need to be interconnected.
This arrangement is useful for interconnecting three-phase and two-phase electrical systems. It produces two equal secondary voltages that are displaced by 90° from each other.
In this article, we will discuss the construction, working principle, phasor diagram, voltage relationships, utility factor, and advantages of the Scott T connection.
Before reading this article, learn more about the three phase transformer connections and open delta connection of transformer.
Construction and Connection
The Scott connection consists of two single-phase transformers:
1. Main Transformer: The main transformer has centre taps on both its primary and secondary windings. These centre taps are used to connect the teaser transformer.
2. Teaser Transformer: The teaser transformer has primary and secondary windings with 86.6% of the turns of the corresponding windings of the main transformer. Both transformers should have the same current rating.
For economical manufacturing, both transformers are generally designed with identical windings and 86.6% tapping points.

The circuit diagram of the Scott connection is shown in above. One end of the primary and secondary windings of the teaser transformer is connected to the centre taps of the primary and secondary windings of the main transformer, respectively.
The remaining terminals are connected to the three-phase supply on the primary side and the load on the secondary side.
Working Principle
Let
,
, and
represent the three-phase supply voltages applied to the transformer terminals, as shown in the below Fig.
Since it is a balanced three phase supply, these voltages are equal in magnitude and 1200 apart. Hence it can be represented by an equivalent triangle.

Since the voltages have the same magnitude, we can write
![]()
Here we have considered,
as the reference phasor, so
![]()
![]()
![]()
The primary winding of the main transformer has a centre tap at point D. So the voltage,
![]()
The voltage across the teaser transformer can be calculated as follows:
![]()
![]()
![]()
![]()
Therefore,
![]()
This shows that the voltage applied to the teaser transformer is 86.6% of the voltage applied to the main transformer and is displaced by 90°.
Since the teaser transformer has 86.6% of the turns of the main transformer, the induced secondary voltage also maintains the same magnitude and phase relationship. Hence, the teaser secondary voltage is 86.6% of the main transformer secondary voltage and is displaced by 90°.
As a result, a balanced two-phase voltage supply is obtained at the secondary terminals.
Rating and Utility Factor
Let
be the line voltage and
be the rated winding current or the line current. The total volt-ampere (VA) rating of the two transformers is:
![]()
![]()
The total VA supplied to the three-phase load is:
![]()
Therefore, the utility factor is:
![]()
![]()
Thus, the Scott connection has a utility factor of 0.928, which is higher than the 0.866 utility factor of the open-delta (V-V) connection.
However, in practical applications, both transformers are generally manufactured with identical ratings to make them interchangeable.
Either transformer can then be used as the main or teaser transformer, although 13.4% of the winding remains unused when operating as a teaser transformer.
In this case, the combined VA rating becomes:
![]()
The utility factor is:
![]()
![]()
Therefore, when identical transformers are used, each transformer must have approximately 15% higher capacity than an individual transformer in a three-transformer bank.
Power Factor and Load Conditions
When the Scott connection supplies a balanced load at a lagging power factor of
, the teaser transformer operates at the same power factor.
However, the two halves of the main transformer operate at different power factors:
- One half operates at
. - The other half operates at
.
This unequal loading is similar to the condition found in an open-delta connection. Due to this difference in loading, the secondary voltages may become increasingly unbalanced as the load increases.
Advantage of Scott Connection
An important advantage of the Scott T connection of transformer is that it can provide a three-phase, four-wire supply. Three-phase loads can be connected across the three line terminals (a, b, and c), while single-phase lighting loads can be connected between the line and neutral terminals.
The neutral connection available in the teaser transformer makes it possible to obtain a three-phase, four-wire system using only two transformers. This is an additional advantage over the open-delta connection.